Siemens SKD60 Valve Actuator

USD 962.69

AC 24 V electro-hydraulic actuator, 1000 N, 20 mm stroke, DC 0…10 V / 4…20 mA / 0…1000 Ω, IP54, Modbus RTU option.

SKU Siemens-SKD60 Category
Top Brands > Siemens > Siemens Valve Actuators

Siemens SKD60 Valve Actuator

Model Identifier SKD60
Official Part Number SKD60
GTIN Standard 7612914018526

Technical Overview

AC 24 V electro-hydraulic actuator, 1000 N, 20 mm stroke, DC 0...10 V / 4...20 mA / 0...1000 Ω, IP54, Modbus RTU option.

Key Features

  • Electro-hydraulic actuator for direct valve mounting
  • AC 24 V supply for modulating control
  • Supports DC 0...10 V, DC 4...20 mA, and 0...1000 Ω signals
  • 1000 N positioning force
  • 20 mm nominal stroke
  • Selectable linear or equal-percentage flow characteristic
  • Stroke calibration for commissioning
  • LED operational and fault indication
  • Override control input Z
  • Optional spring-return versions available
  • Accessory support for auxiliary switches, potentiometer, stem heater, and stroke inverter
  • SKD62UA supports stroke limit control, sequence control, and frost protection monitor signal addition
  • SKD62/MO supports Modbus RTU RS-485 communication

1000 N electro-hydraulic actuation with 20 mm stroke, position feedback, and configurable control behavior.

Technical Specification Matrix

ParameterValue
Operating voltageAC 24 V ± 20 % (SELV/PELV)
Frequency50 / 60 Hz
Positioning signalDC 0...10 V / DC 4...20 mA / 0...1000 Ω
Positioning force1000 N
Nominal stroke20 mm
Positioning time at 50 HzOpening 30 s; Closing 15 s
Spring-return time15 s
Maximum permissible medium temperature-25...150 °C
Input impedance (DC 0...10 V)100 kΩ
Input impedance (DC 4...20 mA)240 Ω
Signal resolution< 1 %
Hysteresis1 %
Override control resistor range0...1000 Ω
Position feedback load impedance (DC 0...9.8 V)> 10 kΩ
Position feedback load impedance (DC 4...19.6 mA)< 500 Ω
Control signal selectionDirect-acting / reverse-acting
Stroke limit control range0...45 % adjustable / 100...55 % adjustable
Sequence control start point0...15 V adjustable
Sequence control operating range3...15 V adjustable
Modbus communication protocolModbus RTU RS-485, not galvanically isolated
Number of nodesMax. 32
Address range1...245 / 255
Transmission formats1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Baud rateAuto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2 kBaud
Bus termination120 Ω electronically switchable
Wire cross-sectional area0.5...2.5 mm² / AWG 21...14
Cable inlet4 x M20 (∅ 20.5 mm)
SKD..U conduit knockoutFor standard ½" conduit connectors (∅ 21.5 mm)
Fixed connection cable length (SKD62/MO)0.9 m
Number of wires (SKD62/MO)5 x 0.75 mm²
Protection classAs per EN 60730
Pollution degree2
Housing protectionIP54 as per EN 60529
Operating climateIEC 60721-3-3, Class 3K5
Operating temperature-15...50 °C
Operating humidity5...95 % r.h. non-condensing
Transportation climateIEC 60721-3-2, Class 2K3
Transportation temperature-30...65 °C
Storage climateIEC 60721-3-1, Class 1K3
Storage temperature-15...50 °C
Housing materialDie-cast aluminium
Bracket materialPlastic
Housing box materialPlastic
Hand crank materialPlastic
Weight3.60 kg (SKD60)
Height300 mm from plate without ASK50; 357 mm with ASK50
Width127 mm
Depth105 mm
Footprint width120 mm
Lower body width66 mm
Connection clearance> 100 mm from ceiling or wall; > 200 mm for connection/maintenance
Physical Weight (kg)3.6
Dimensions L x W x H (cm)17.5 x 20.5 x 33.5

Industrial Applications

1. HVAC control of 20 mm stroke control valves

Ideal for modulating chilled water, heating water, or air-handling coil valves where precise 20 mm valve travel and 1000 N thrust are required.

Problem Solved

Provides stable proportional control of valve position under varying differential pressure and load conditions.

AC 24 V20 mm stroke1000 NDC 0...10 VDC 4...20 mAHVAC valves

2. Frost-protection valve control in air-handling units

Used with frost protection thermostats or QAF21/QAF61 monitors to drive the valve toward a protective position when freeze risk is detected.

Problem Solved

Prevents coil freeze damage by forcing a coordinated protective stroke response.

frost protection monitorsequence controlsignal additionQAF21QAF61spring-return

3. Building automation with fieldbus valve actuation

SKD62/MO fits distributed building automation systems that require RS-485 Modbus RTU integration for remote command and status feedback.

Problem Solved

Reduces analog I/O wiring and enables supervisory control, status polling, and networked commissioning.

Modbus RTURS-485AC 24 Vposition feedbackbuilding automationremote valve control