SIMATIC S7-1200 – SB 1231 RTD – Siemens Signal/ Communication Boards
USD 149.78
The SB 1231 RTD signal board permits temperature recording with high precision using resistance temperature detectors. The SB 1231 RTD signal board can be used with SIMATIC S7-1200 CPUs. The SB 1231 RTD signal board can be plugged directly into all SIMATIC S7-1200 CPUs.
Siemens Signal Boards S7-1200 Product Specifications:
| Article number | 6ES7231-5PA30-0XB0 | |
| Signal Board SB 1231 RTD | ||
| General information | ||
| Product type designation | SB 1231, AI 1×16 bit RTD | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| Input current | ||
| Current consumption, typ. | 5 mA | |
| from backplane bus 5 V DC, typ. | 20 mA | |
| Power loss | ||
| Power loss, typ. | 0.5 W | |
| Analog inputs | ||
| Number of analog inputs | 1; Resistance thermometer | |
| permissible input voltage for current input (destruction limit), max. | ±35 V | |
| Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit | |
| Input ranges | ||
| ● Voltage | Yes | |
| ● Current | No | |
| ● Thermocouple | No | |
| ● Resistance thermometer | Yes; Platinum (Pt) | |
| ● Resistance | Yes; 150 Ω, 300 Ω, 600 Ω | |
| Input ranges (rated values), voltages | ||
| ● -80 mV to +80 mV | ||
| — Input resistance (-80 mV to +80 mV) | >= 10 MOhm | |
| Input ranges (rated values), resistance thermometer | ||
| ● Pt 100 | Yes | |
| — Input resistance (Pt 100) | 100 Ω | |
| ● Pt 1000 | Yes | |
| — Input resistance (Pt 1000) | 1 000 Ω | |
| ● Pt 200 | Yes | |
| — Input resistance (Pt 200) | 200 Ω | |
| ● Pt 500 | Yes | |
| — Input resistance (Pt 500) | 500 Ω | |
| Input ranges (rated values), resistors | ||
| ● 0 to 150 ohms | Yes | |
| ● 0 to 300 ohms | Yes | |
| ● 0 to 600 ohms | Yes | |
| Thermocouple (TC) | ||
| Temperature compensation | ||
| — parameterizable | No | |
| Analog outputs | ||
| Number of analog outputs | 0 | |
| Cable length | ||
| ● shielded, max. | 100 m; shielded, twisted pair | |
| Analog value generation for the inputs | ||
| Measurement principle | integrating | |
| Integration and conversion time/resolution per channel | ||
| ● Resolution with overrange (bit including sign), max. | 15 bit; + sign | |
| ● Integration time, parameterizable | No | |
| ● Interference voltage suppression for interference frequency f1 in Hz | 85 dB at 10 / 50 / 60 / 400 Hz | |
| Errors/accuracies | ||
| Temperature error (relative to input range), (+/-) | 25 °C ±0.1%, to 55 °C ±0.2% total measurement range | |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % | |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
| ● Common mode interference, min. | 120 dB | |
| Interrupts/diagnostics/status information | ||
| Alarms | Yes | |
| Diagnostics function | Yes; Can be read out | |
| Alarms | ||
| ● Diagnostic alarm | Yes | |
| Diagnoses | ||
| ● Wire-break | Yes | |
| Diagnostics indication LED | ||
| ● for status of the inputs | Yes | |
| ● for maintenance | Yes | |
| Standards, approvals, certificates | ||
| CE mark | Yes | |
| CSA approval | Yes | |
| UL approval | Yes | |
| cULus | Yes | |
| FM approval | Yes | |
| RCM (formerly C-TICK) | Yes | |
| KC approval | Yes | |
| Marine approval | Yes | |
| Ambient conditions | ||
| Free fall | ||
| ● Fall height, max. | 0.3 m; five times, in product package | |
| Ambient temperature during operation | ||
| ● min. | -20 °C | |
| ● max. | 60 °C | |
| ● horizontal installation, min. | -20 °C | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | -20 °C | |
| ● vertical installation, max. | 50 °C | |
| Ambient temperature during storage/transportation | ||
| ● min. | -40 °C | |
| ● max. | 70 °C | |
| Air pressure acc. to IEC 60068-2-13 | ||
| ● Operation, min. | 795 hPa | |
| ● Operation, max. | 1 080 hPa | |
| ● Storage/transport, min. | 660 hPa | |
| ● Storage/transport, max. | 1 080 hPa | |
| Relative humidity | ||
| ● Operation at 25 ℃ without condensation, max. | 95 % | |
| Pollutant concentrations | ||
| ● SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | |
| connection method / header | ||
| required front connector | Yes | |
| Mechanics/material | ||
| Enclosure material (front) | ||
| ● Plastic | Yes | |
| Dimensions | ||
| Width | 38 mm | |
| Height | 62 mm | |
| Depth | 21 mm | |
| Weights | ||
| Weight, approx. | 35 g | |