SICK 1041040 IME30-15BNSZW2S NPN Inductive Sensor

USD 43.42

IME30-15BNSZW2S offers 15 mm nominal and 12.15 mm assured sensing, flush M30 mounting, NPN normally-open output and a 2 m three-wire PVC cable.

SKU SICK-1041040 Category
SICK IME

SICK IME30-15BNSZW2S NPN Flush Inductive Proximity Sensor

BrandSICK
Model IdentifierIME30-15BNSZW2S
Official Part Number1041040

Technical Overview

The SICK IME30-15BNSZW2S is a standard-design M30 × 1.5 inductive proximity sensor for flush installation. Nominal sensing range is 15 mm and assured sensing range is 12.15 mm, with material-dependent reduction factors for nonferrous and stainless targets. Its NPN normally-open output switches at up to 500 Hz and supports continuous current up to 200 mA. The 10–30 V DC three-wire device connects through a 2 m three-wire PVC cable with 0.25 mm² conductors and a 3.9 mm diameter. A nickel-plated brass housing and PA66 sensing face provide IP67 protection. Two nickel-plated brass mounting nuts are supplied. Operating temperature spans −25 to +75 °C, and maximum tightening torque is 100 Nm.

Flush standard-design M30 inductive sensor with 15 mm nominal range, 12.15 mm assured range, NPN normally-open output and a 2 m three-wire PVC cable.

Key Features

  • Inductive proximity sensing; standard-design M30 × 1.5 housing; flush installation
  • 15 mm nominal sensing range; 12.15 mm assured sensing range
  • NPN normally-open output; DC three-wire configuration
  • 500 Hz switching frequency; continuous output current ≤200 mA
  • 10–30 V DC; no-load current ≤10 mA; voltage drop ≤2 V at maximum load
  • ≤125 ms time delay before availability; short-circuit and power-up pulse protection
  • 2 m three-wire PVC cable; 0.25 mm² conductors; 3.9 mm diameter
  • Nickel-plated brass housing; PA66 sensing face; IP67
  • Two nickel-plated brass mounting nuts supplied; 36 mm across flats
  • −25 to +75 °C operation; tightening torque ≤100 Nm

Detect a metal target at a flush sensing face and supply an NPN normally-open signal to external counting, fixture or position-monitoring logic.

Technical Specification Matrix

ParameterValue
Functional principleInductive proximity sensor
Housing designMetric standard-design
Mounting threadM30 × 1.5
InstallationFlush
Nominal sensing range Sn15 mm
Assured sensing range Sa12.15 mm
Switching outputNPN
Output functionNormally open (NO)
Electrical wiringDC three-wire
Switching frequency500 Hz
Power supply10–30 V DC
Ripple≤10%
Voltage drop≤2 V at maximum output current
Time delay before availability≤125 ms
Hysteresis3–15%
Reproducibility≤2% of real sensing range Sr at constant supply voltage and ambient temperature
Temperature drift±10% of real sensing range Sr
Continuous output current≤200 mA
No-load current≤10 mA
Short-circuit protectionProvided
Power-up pulse protectionProvided
Connection2 m three-wire PVC cable
Conductor cross-section0.25 mm²
Cable diameter3.9 mm
Wire assignmentsCD-001: BN=L+; BK=normally-open output; BU=M
Housing materialNickel-plated brass
Sensing face materialPA66 plastic
Housing length70 mm
Thread length54 mm
Tightening torque≤100 Nm
IP ratingIP67 according to EN 60529
Items suppliedTwo nickel-plated brass mounting nuts; 36 mm across flats
IndicatorDisplay LED
Operating temperature−25 to +75 °C
Shock resistance30 g, 11 ms
Vibration resistance10–55 Hz, 1 mm amplitude
EMCAccording to EN 60947-5-2
UL fileNRKH.E181493
MTTFD1,735 years
DCavg0%
Material reduction factorsReference values, may vary: St37 steel 1; stainless steel V2A/304 approximately 0.8; aluminum approximately 0.45; copper approximately 0.4; brass approximately 0.4

Industrial Applications

1. Confirming a metal clamp at its seated position

A fixture can present a metal clamp target to the flush sensing face at a controlled final gap. External sequencing logic samples the NPN normally-open output after the clamp settles. Commissioning checks target material, thickness and placement tolerance against the nominal and assured ranges, accounting for material reduction factors before accepting the seated condition.

Problem Solved

A clamp-position reference helps external sequencing logic distinguish a seated metal target from an open location, using a flush inductive sensing point checked for the actual target material.

Clamp presence Flush installation NPN output

2. Counting separated metal flags on a moving mechanism

A moving mechanism can carry separated metal flags past the inductive sensing face and feed NPN transitions to external counting electronics. Setup checks flag material, coverage, passing gap and the separation between flags. Motion timing is verified against the 500 Hz switching frequency, and the connected input respects the continuous-current and voltage-drop limits.

Problem Solved

A metal-flag passage reference helps external counting electronics register repeated mechanical events, using contactless inductive switching checked for the actual target spacing, material and travel speed.

Metal-flag counting Inductive switching Timing checks

3. Referencing a carriage near a travel position

A carriage can bring a metal reference tab toward the flush-mounted sensor near a defined travel position. External motion logic reads the NPN normally-open state as a position reference. Installation checks tab material, approach geometry and allowable gap, while commissioning accounts for reproducibility, hysteresis and temperature drift so the reference remains meaningful over the expected operating conditions.

Problem Solved

A carriage-reference signal helps external motion logic identify a checked mechanical position, using inductive target detection and installation margins established for the actual approach geometry and temperature range.

Carriage reference Metal target Installation margins