| Type of mounting | On DIN rail via accessories; With through-hole |
| Physical Weight (kg) | 0.126 |
| Ambient temperature | -20 °C...60 °C |
| Storage temperature | -40 °C...70 °C |
| Relative air humidity | 5 - 95%; Non-condensing |
| Degree of protection | IP65; IP67 |
| Note on degree of protection | Unused connections sealed |
| Corrosion resistance class CRC | 1 - Low corrosion stress |
| Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN; 60068-2-6 |
| Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Pollution degree | 2 |
| Overvoltage category | II |
| Max. cable length | 30 m inputs; 50 m system communication |
| Note on max. cable length | Power supply according to nominal voltage |
| LABS (PWIS) conformity | VDMA24364-B2-L |
| Cleanroom suitability, measured according to ISO 14644-14 | Element installed statically, no meaningful evaluation possible according; to ISO 14644-1 |
| CE mark (see declaration of conformity) | To EU EMC Directive; In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK instructions for EMC; To UK RoHS instructions |
| KC mark | KC-EMV |
| Approval | RCM; c UL us - Listed (Oil) |
| Certificate issuing authority | UL E239998 |
| Note on materials | RoHS compliant |
| Material housing | PA; Makrolon®; Nickel-plated die-cast zinc |
| Material o-ring | Fluoro rubber |
| Diagnostics via LED | Diagnostics per module; Status per channel |
| Diagnostics per internal communication | Short circuit/overload in sensor supply; Electronics/sensors overvoltage; Electronics/sensors undervoltage |
| Communication interface, function | System communication XF10 IN / XF20 OUT |
| Communication interface, connection type | 2x socket |
| Communication interface, connection technology | M8x1, D-coded according to EN 61076-2-114 |
| Communication interface, number of pins/cores | 4 |
| Communication interface, protocol | AP |
| Communication interface, screened | Yes |
| Power supply, function | Incoming electronics/sensors and load |
| Power supply, connection type | Plug |
| power supply, connection system | M8x1, A-coded to EN 61076-2-104 |
| Power supply, number of pins/wires | 4 |
| Power transmission, function | Outgoing electronics/sensors and load |
| Power transmission, connection type | Socket |
| Power transmission, connection technology | M8x1, A-coded to EN 61076-2-104 |
| Power transmission, number of pins/wires | 4 |
| Note regarding operating voltage | SELV/PELV fixed power supplies required; Note the voltage drop |
| Nominal DC operating voltage, electronics/sensors | 24 V |
| Permissible voltage fluctuations for electronics/sensors | ±25% |
| Max. power supply | 2 x 4 A (external fuse required) |
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 32 mA |
| Power failure bridging | 10 ms |
| Reverse polarity protection | Yes |
| Electrical connection input, function | Digital input |
| Electrical connection input, connection type | 8x socket |
| Electrical connection input, connector system | M8x1, A-coded to EN 61076-2-104 |
| Electrical connection input, number of connections/cores | 3 |
| Number of inputs | 8 |
| Characteristic for inputs | To IEC 61131-2, type 3 |
| Switching level | Signal 0: <= 5 V; Signal 1: ≥ 11 V |
| Switching logic for inputs | PNP (positive switching); 2-wire sensors to IEC 61131-2; 3-wire sensors to IEC 61131-2 |
| Input debounce time | 0.1 ms; 3 ms; 10 ms; 20 ms |
| Fuse protection of inputs (short circuit) | Internal electronic fuse per module |
| Max. residual current of inputs per module | 1.8 A |
| Electrical isolation of inputs between channels | No |
| Electrical isolation of inputs between channel – internal communication | Yes |
| Dimensions L x W x H (cm) | 17 x 3 x 3.5 |