Sale!

Festo 572556 CTEU-EC EtherCAT Bus Node, 24 V DC

Original price was: USD 185.90.Current price is: USD 160.16.

EtherCAT bus node with two D-coded M12 sockets, 100 Mbit/s isolated Ethernet, 16-byte input/output address limits, diagnostics and 18–30 V DC supply.

Festo Remote I/O and Network Interface Components

Festo CTEU-EC EtherCAT Bus Node

BrandFesto
Model IdentifierCTEU-EC
Official Part Number572556

Technical Overview

The Festo CTEU-EC connects compatible I-Port equipment to an EtherCAT network through an electrically isolated 100 Mbit/s Ethernet interface. Two four-contact D-coded M12 sockets provide the fieldbus connections, with maximum input and output address volumes of 16 bytes each. Communication errors, undervoltage and system diagnostics are accompanied by supply, I-Port, link/activity and run LEDs. The node supports XML configuration files, acyclic SDO access, diagnostic objects, emergency messages and a modular device profile. Its five-pin A-coded M12 power input operates at 18–30 V DC, nominally 24 V DC. The 90 g PA-housed module has IP65/IP67 protection when mounted with unused connections sealed.

EtherCAT bus node with two D-coded M12 network sockets, 100 Mbit/s isolated interface, 16-byte input/output address limits and 18–30 V DC supply.

Key Features

  • EtherCAT protocol over a 100 Mbit/s Ethernet fieldbus interface
  • Two four-contact D-coded M12×1 sockets to EN 61076-2-101
  • Electrically isolated fieldbus interface
  • Maximum input and output address volumes of 16 bytes each
  • Internal cycle time: 1 ms per user-data byte
  • XML configuration support and DIL operating controls
  • Acyclic SDO access, diagnostic object, emergency message and modular device profile
  • Communication-error, undervoltage and system diagnostics with local LEDs
  • Five-pin A-coded M12 power input; 18–30 V DC, nominal 24 V DC and maximum 4 A supply
  • 90 g product weight; IP65/IP67 when mounted with unused connections sealed

Connect compatible I-Port equipment to EtherCAT with two M12 network sockets, isolated Ethernet and local communication diagnostics.

Technical Specification Matrix

ParameterValue
ProtocolEtherCAT®
Mounting grid pitch40 mm
Type of mountingOn electrical interface; On electrical connection block
Physical Weight (kg)0.09
Ambient temperature0 °C...50 °C
Storage temperature-20 °C...70 °C
Degree of protectionIP65; IP67
Note on degree of protectionIn mounted state; Unused connections sealed
Corrosion resistance class CRC2 - Moderate corrosion stress
LABS (PWIS) conformityVDMA24364 zone III
CE mark (see declaration of conformity)To EU EMC Directive; In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC; To UK RoHS instructions
KC markKC-EMV
ApprovalRCM; c UL us - Listed (Oil)
Note on materialsRoHS compliant
Material housingPA
LED display, product-specificPS: Operating voltage for electronics and load supply; X1: System status of module at I-Port 1; X2: System status of module at I-Port 2
LED display, bus-specificL/A1: Network active port 1; L/A2: Network active port 2; Run: Communication status
DiagnosisCommunication error; System diagnostics; Undervoltage
Operator controlsDIL switch
Fieldbus interfaceEthernet
Field bus, protocolEtherCAT®
Field bus, connection type2x socket
Field bus, connection systemM12x1, D-coded to EN 61076-2-101
Field bus, connection pattern4
Field bus interface, electrical isolationYes
Field bus interface, transmission rate100 Mbit/s
Max. address volume, inputs16 Byte
Max. address volume, outputs16 Byte
ParameterisationActivating diagnostics; Fail-safe and idle response
Internal cycle time1 ms per 1 byte of user data
Configuration supportXML file
Additional functionsAcyclic data access via SDO; Diagnostics object; Emergency message; Modular device profile (MDP)
Power supply, functionElectronics and load
Power supply, connection typePlug
power supply, connection systemM12x1, A-coded according to EN 61076-2-101
Power supply, number of pins/wires5
Operational voltage range DC18 V...30 V
Nominal operating voltage DC24 V
Max. power supply4 A
Intern power consumption nominal operating voltageTyp. 60 mA
Dimensions L x W x H (cm)9.1 x 4 x 5

Industrial Applications

1. EtherCAT Integration of a Valve Terminal

A machine with an EtherCAT master needs to command a compatible Festo valve terminal through its I-Port interface. The CTEU-EC supplies the network connection using two D-coded M12 sockets and an electrically isolated 100 Mbit/s Ethernet interface. Its maximum 16-byte input and output address volumes define the listed capacity for configuring the terminal process-data exchange.

Problem Solved

The bus node translates between the EtherCAT network connection and compatible I-Port equipment, providing a documented communication path for valve commands and the terminal's associated process information.

EtherCAT I-Port equipment Isolated Ethernet

2. Diagnostic Access for a Pneumatic Station

A controller needs more than the ordinary valve commands when investigating a station communication or supply problem. The CTEU-EC lists acyclic SDO access, a diagnostic object and emergency messages, alongside communication-error, undervoltage and system diagnostics. Local PS, X1, X2, link/activity and run indicators expose supply, connected-module and network conditions at the machine.

Problem Solved

Diagnostic services and local indicators give the control system and maintenance personnel documented ways to observe communication and supply conditions around the connected I-Port station.

SDO access Diagnostic object Local LEDs

3. Configured Response to Bus Idle or Communication Loss

A machine sequence needs its connected equipment's behaviour defined when the network is idle or a communication problem occurs. The CTEU-EC lists parameterisation for fail-safe and idle response together with activation of diagnostics. DIL switches provide the local operating controls, while link/activity and run indicators expose the communication condition during commissioning and ordinary fault investigation.

Problem Solved

Configurable idle and communication-loss responses give the station a defined operational parameter set for those network conditions, with diagnostic indication supporting verification during commissioning.

Idle response parameters DIL controls Bus diagnostics
Select your currency