| Mounting grid pitch | 18.9 mm |
| Type of mounting | via DIN rail |
| Physical Weight (kg) | 0.093 |
| Mounting position | Vertical; Horizontal |
| Ambient temperature | -5 °C...50 °C |
| Note on ambient temperature | -5 - 60°C for vertical installation |
| Storage temperature | -20 °C...70 °C |
| Relative air humidity | 95%; Non-condensing |
| Degree of protection | IP20 |
| Corrosion resistance class CRC | 0 - No corrosion stress |
| Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN; 60068-2-6 |
| Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Protection against direct and indirect contact | PELV |
| Max. cable length | 30 m outputs |
| LABS (PWIS) conformity | VDMA24364 zone III |
| CE mark (see declaration of conformity) | To EU EMC Directive; In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) | To UK instructions for EMC; To UK RoHS instructions |
| KC mark | KC-EMV |
| Approval | RCM; c UL us - Listed (Oil) |
| Certificate issuing authority | UL E239998 |
| Note on materials | RoHS compliant |
| Material housing | PA |
| Diagnostics via LED | Error per channel; Errors per module; Status per channel |
| Diagnostics via bus | Module error; Short circuit/overload at output; Load supply undervoltage |
| Max. address volume, outputs | 1 Byte |
| Number of outputs | 8 |
| Module parameters | Short circuit diagnostics at output; Diagnostics for undervoltage in load supply; Behaviour after short circuit/overload |
| Channel parameters | Force channel x |
| Power supply, connection type | Terminal strip |
| power supply, connection system | Spring-loaded terminal |
| Power supply, number of pins/wires | 4 |
| Nominal operating voltage DC of load | 24 V |
| Permissible voltage fluctuation of load | ±25% |
| Power supply, conductor diameter | 0.2 mm²...1.5 mm² |
| Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Intrinsic current consumption at nominal operating voltage load | Typically 34 mA |
| Reverse polarity protection | 24 V load against 0 V load |
| Electrical connection output, function | Digital output |
| Electrical connection output, connection type | 4x terminal strip |
| Electrical connection output, connector system | Spring-loaded terminal |
| Electrical connection output, number of connections/cores | 4 |
| Electrical connection for output, conductor cross section | 0.2 mm²...1.5 mm² |
| Electrical connection for output, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire ferrule |
| Characteristic for outputs | To IEC 61131-2, type 0.5 |
| Switching logic for outputs | PNP (positive switching) |
| Behaviour after end of overload of the outputs | No automatic return (default); Parameterisable (module by module) |
| Max. residual current outputs per module | 4 A |
| Isolation channel - channel | No |
| Isolation channel - internal bus | Yes |
| Fuse protection (short circuit) | Internal electronic fuse per channel |
| Dimensions L x W x H (cm) | 7.66 x 1.89 x 12.43 |