QUINT-ORING/24DC/2X20/1X40 – 2320186 – Redundancy Module, With Protective Coating – Phoenix Contact Redundancy Modules

$ 243.11

SKU Phoenix Contact 2320186 Category

Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.

Commercial Data

Item number 2320186
Packing unit 1 pc
Minimum order quantity 1 pc
Product key CMRQ43
Catalog page Page 303 (C-4-2019)
GTIN 4046356524919
Weight per piece (including packing) 764.9 g
Weight per piece (excluding packing) 557 g
Customs tariff number 85371091
Country of origin IN

Product Properties

Product type Redundancy module
Product family QUINT ORING
MTBF (IEC 61709, SN 29500) > 720000 h (40 °C)
LED yes
Insulation characteristics
Protection class III
Degree of pollution 2

Electrical Properties

Insulation voltage input, output / housing 500 V

Input Data

DC operation
Nominal input voltage range 24 V DC
Input voltage range 18 V DC … 28 V DC (SELV)
Input voltage range DC 18 V DC … 28 V DC (SELV)
Voltage type of supply voltage DC
Reverse polarity protection < yes60 V
Nominal input current (IN) 2x 20 A (-25 °C … 60 °C)
1x 40 A (-25 °C … 60 °C)
Maximum current Imax 2x 26 A (-25 °C … 40 °C)
1x 52 A (-25 °C … 40 °C)
120 A (12 ms, SFB Technology)
Transient surge protection Varistor
Voltage drop, input/output 0.2 V (IOUT = 40 A)

Output Data

Efficiency > 98 %
Nominal output voltage UIn – 0,2 V
Nominal output current (IN) 40 A (Increasing power)
20 A (Redundancy)
Derating 60 °C … 70 °C (2.5 %/K)
Protection against overvoltage at the output (OVP) < 32 V DC
Power loss nominal load max. 8 W (IOUT = 40 A)
Connection in series no
Signal: Redundancy OK, 13/14
Output description Group contact
Maximum switching voltage max. 30 V AC/DC
Maximum inrush current ≤ 100 mA (short-circuit-proof)
Signal: ACB (Auto Current Balancing) OK, 23/24
Output description Contact closed: Δ UIN ≤ 300 mV
Maximum switching voltage max. 30 V AC/DC
Maximum inrush current ≤ 100 mA (short-circuit-proof)

Connection Data

Input
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 10
Stripping length 8 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section, rigid min. 0.5 mm²
Conductor cross section, rigid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 6
Stripping length 10 mm
Screw thread M4
Tightening torque, min 1.2 Nm
Tightening torque max 1.5 Nm
Signal
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 10
Stripping length 10 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Signaling

Types of signaling Relay contact, floating, current limited
Signal output: Redundancy OK, 13/14
Status display LED redundancy OK
Note on status display green
Color green
Signal output: ACB (Auto Current Balancing) OK, 23/24
Status display ACB OK LED
Note on status display LED bar graph green
Color green
Note on status display LED bar graph green

Dimension

Width 38 mm
Height 130 mm
Depth 125 mm
Horizontal pitch 2.1 Div.
Installation dimensions
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Alternative assembly
Width 122 mm
Height 130 mm
Depth 41 mm

Material Specifications

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Galvanized sheet steel, free from chrome (VI)

Environmental and real-life conditions 

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Maximum altitude 2000 m
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 100 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz … 150 Hz, 2.3g, 90 min.
Temp code T4 (-25 … +70 °C; > 60 °C, Derating: 2,5 %/K)

Standards And Regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Noxious gas test ISA-S71.04-1985 G3 Harsh Group A

Approvals

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T3C … T4 (Hazardous Location)
Conformity/Approvals
ATEX  II 3 G  Ex ec nC IIC T4 Gc
DEKRA 20ATEX0136 X
IECEx Ex ec nC IIC T4 Gc
DEK 20.0082X

EMC Data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz … 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz … 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz … 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 – asymmetrical)
Output 2 kV (Test Level 3 – asymmetrical)
Signal 2 kV (Test Level 4 – asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Surge voltage load (surge)
Input 0.5 kV (Test Level 1 – symmetrical)
0.5 kV (Test Level 1 – asymmetrical)
Output 0.5 kV (Test Level 1 – symmetrical)
0.5 kV (Test Level 1 – asymmetrical)
Signal 1 kV (Test Level 2 – asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Input/output/signal asymmetrical
Frequency range 0.15 MHz … 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Mounting

Mounting type DIN rail mounting
Assembly note alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position horizontal DIN rail NS 35, EN 60715

Additional information

Weight 0.7649 kg
Dimensions 12.5 × 3.8 × 13 cm

Related Products

EE-SPY31 41
IDS_camera_UI-5240SE Rev
Mitutoyo_Absolute Digimatic Indicators_ 543-701B
MOXA_Unmanaged_Switches_MOXA EDS-G205-1GTXSFP-T
Mitutoyo_Digital Micrometer_293-241-30
MOXA_Unmanaged_Switches_MOXA_EDS-2005-ELP
Select your currency