Sale!

Festo 8086602 CPX-AP-I Digital Input Module, 8 PNP, M12

Original price was: USD 310.70.Current price is: USD 267.28.

Eight-input AP module with four five-pin M12 sockets, IEC 61131-2 type 3 PNP inputs, selectable debounce, 24 V DC supply and IP65/IP67 protection.

Festo Remote I/O and Network Interface Components

Festo CPX-AP-I-8DI-M12-5P Digital Input Module

BrandFesto
Model IdentifierCPX-AP-I-8DI-M12-5P
Official Part Number8086602

Technical Overview

The Festo CPX-AP-I-8DI-M12-5P acquires eight positive-switching digital inputs through four five-pin A-coded M12 sockets. Its IEC 61131-2 type 3 inputs support compatible two- or three-wire sensors, with listed debounce times of 0.1, 3, 10 and 20 ms. One byte of input address space represents the module's channels. D-coded M8 AP input/output connections integrate system communication, while M8 power input and forwarding support the nominal 24 V DC electronics/sensor circuit. Channel LEDs, module diagnostics and an internal electronic sensor-supply fuse support fault investigation. The 126 g module offers IP65/IP67 protection with unused connections sealed and operates over −20 to 60 °C.

Eight-channel PNP digital input module for CPX-AP-I with four five-pin M12 sockets, selectable debounce and IP65/IP67 protection.

Key Features

  • Eight PNP positive-switching digital inputs to IEC 61131-2 type 3
  • Four five-pin A-coded M12x1 input sockets
  • Supports compatible two-wire and three-wire sensors
  • Listed input debounce times: 0.1, 3, 10 and 20 ms
  • Signal 0 at ≤5 V; signal 1 at ≥11 V
  • One-byte input address volume and M8 AP system input/output connections
  • Internal electronic fuse per module with sensor-supply diagnostics
  • Input channels isolated from internal communication; no isolation between channels
  • Nominal 24 V DC electronics/sensor power; maximum 2 × 4 A power feed with external fusing
  • 126 g product weight; IP65/IP67 with unused connections sealed and −20 to 60 °C ambient range

Collect eight PNP sensor signals at the machine through M12 connections, with selectable debounce and per-channel LED indication.

Technical Specification Matrix

ParameterValue
Type of mountingOn DIN rail via accessories; With through-hole
Physical Weight (kg)0.126
Ambient temperature-20 °C...60 °C
Storage temperature-40 °C...70 °C
Relative air humidity5 - 95%; Non-condensing
Degree of protectionIP65; IP67
Note on degree of protectionUnused connections sealed
Corrosion resistance class CRC1 - Low corrosion stress
Vibration resistanceTransport application test with severity level 1 to FN 942017-4 and EN; 60068-2-6
Shock resistanceShock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Pollution degree2
Overvoltage categoryII
Max. cable length30 m inputs; 50 m system communication
Note on max. cable lengthPower supply according to nominal voltage
LABS (PWIS) conformityVDMA24364-B2-L
Cleanroom suitability, measured according to ISO 14644-14Element installed statically, no meaningful evaluation possible according; to ISO 14644-1
CE mark (see declaration of conformity)To EU EMC Directive; In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC; To UK RoHS instructions
KC markKC-EMV
ApprovalRCM; c UL us - Listed (Oil)
Certificate issuing authorityUL E239998
Note on materialsRoHS compliant
Material housingPA; Makrolon®; Nickel-plated die-cast zinc
Material o-ringFluoro rubber
Diagnostics via LEDDiagnostics per module; Status per channel
Diagnostics per internal communicationShort circuit/overload in sensor supply; Electronics/sensors overvoltage; Electronics/sensors undervoltage
Max. address volume, inputs1 Byte
Communication interface, functionSystem communication XF10 IN / XF20 OUT
Communication interface, connection type2x socket
Communication interface, connection technologyM8x1, D-coded according to EN 61076-2-114
Communication interface, number of pins/cores4
Communication interface, protocolAP
Communication interface, screenedYes
Power supply, functionIncoming electronics/sensors and load
Power supply, connection typePlug
power supply, connection systemM8x1, A-coded to EN 61076-2-104
Power supply, number of pins/wires4
Power transmission, functionOutgoing electronics/sensors and load
Power transmission, connection typeSocket
Power transmission, connection technologyM8x1, A-coded to EN 61076-2-104
Power transmission, number of pins/wires4
Note regarding operating voltageSELV/PELV fixed power supplies required; Note the voltage drop
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors±25%
Max. power supply2 x 4 A (external fuse required)
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 32 mA
Power failure bridging10 ms
Reverse polarity protectionYes
Electrical connection input, functionDigital input
Electrical connection input, connection type4x socket
Electrical connection input, connector systemM12x1, A-coded to EN 61076-2-101
Electrical connection input, number of connections/cores5
Number of inputs8
Characteristic for inputsTo IEC 61131-2, type 3
Switching levelSignal 0: <= 5 V; Signal 1: ≥ 11 V
Switching logic for inputsPNP (positive switching); 2-wire sensors to IEC 61131-2; 3-wire sensors to IEC 61131-2
Input debounce time0.1 ms; 3 ms; 10 ms; 20 ms
Fuse protection of inputs (short circuit)Internal electronic fuse per module
Max. residual current of inputs per module1.8 A
Electrical isolation of inputs between channelsNo
Electrical isolation of inputs between channel – internal communicationYes
Dimensions L x W x H (cm)17 x 3 x 3.5

Industrial Applications

1. Distributed Position-Sensor Acquisition

A machine station needs to collect several compatible PNP proximity-switch signals near its pneumatic drives. The module provides eight digital inputs through four M12 sockets, with a one-byte input address volume for AP communication. Its support for two- and three-wire sensors defines the documented input-device options, while channel LEDs provide local indication during operation and commissioning.

Problem Solved

The module gathers multiple position-switch signals at a local AP connection point, providing process inputs and channel indication for coordinating the station's ordinary machine sequence.

Eight PNP inputs M12 connections One-byte input data

2. Input Debounce for Process Switching Signals

A process sensor can produce brief transitions that the machine should treat differently from a sustained state change. This module lists debounce settings of 0.1, 3, 10 and 20 ms, allowing the input response to be matched to the required process timing. IEC type 3 characteristics and defined high/low voltage thresholds specify how the electrical signal is interpreted.

Problem Solved

Adjustable debounce provides a defined temporal filter for the input state, helping the machine distinguish brief transitions from the sustained switching condition needed by its sequence.

0.1–20 ms listed debounce IEC type 3 Defined voltage thresholds

3. Sensor-supply Fault Identification at the Machine

A station loses several sensor signals and maintenance needs to determine whether the problem is a process state or the module's sensor supply. Internal communication diagnostics report sensor-supply short circuit or overload and electronics/sensor overvoltage or undervoltage. Module and channel LEDs provide local information, while the internal electronic fuse per module supplies the documented short-circuit protection arrangement.

Problem Solved

Supply diagnostics distinguish electrical supply faults from ordinary input states, directing fault investigation toward the affected wiring or power condition when multiple sensor signals are lost.

Sensor-supply diagnostics Electronic fuse Channel LEDs