Festo 4080492 CPX-E-16DI Digital Input Module, 16 PNP Inputs

USD 1,120.86

Sixteen-channel CPX-E input module for 24 V DC PNP sensors with selectable debounce, signal extension, spring terminals and sensor-supply diagnostics.

Festo Remote I/O and Network Interface Components

Festo CPX-E-16DI Digital Input Module

BrandFesto
Model IdentifierCPX-E-16DI
Official Part Number4080492

Technical Overview

The Festo CPX-E-16DI adds sixteen positive-switching digital inputs to a compatible CPX-E automation system. IEC 61131-2 type 3 input characteristics support two- and three-wire sensors, with signal-zero levels up to 5 V and signal-one levels from 11 V. Eight spring-terminal strips provide two inputs each, and the input address capacity is two bytes. Selectable debounce times of 0.1, 3, 10 or 20 ms and signal-extension parameters support adapting input evaluation to the machine signals. An electronic fuse protects the sensor supply per module, with short-circuit/overload bus diagnostics and channel-state LEDs. The 102 g PA module mounts on a DIN rail with IP20 protection and 30 m maximum input cables.

Sixteen-channel CPX-E digital input module for 24 V DC PNP two- and three-wire sensors with debounce settings, signal extension and IP20 protection.

Key Features

  • Sixteen PNP positive-switching digital inputs
  • Two-byte input address capacity
  • IEC 61131-2 type 3 input characteristics for two- and three-wire sensors
  • Nominal 24 V DC electronics/sensor supply with ±25% voltage tolerance
  • Signal 0 at up to 5 V; signal 1 from 11 V
  • Selectable input debounce: 0.1, 3, 10 or 20 ms
  • Signal-extension module timing and per-channel enable parameters
  • Sensor-supply electronic fuse per module; short-circuit/overload diagnostics
  • Eight six-contact spring-terminal strips, with two inputs each
  • 102 g PA DIN-rail module, IP20, with 30 m maximum input cable length

Acquire sixteen compatible sensor signals in CPX-E with configurable debounce, signal extension and local channel-state indication.

Technical Specification Matrix

ParameterValue
Mounting grid pitch18.9 mm
Type of mountingvia DIN rail
Physical Weight (kg)0.102
Mounting positionVertical; Horizontal
Ambient temperature-5 °C...50 °C
Note on ambient temperature-5 - 60°C for vertical installation
Storage temperature-20 °C...70 °C
Relative air humidity95%; Non-condensing
Degree of protectionIP20
Corrosion resistance class CRC0 - No corrosion stress
Vibration resistanceTransport application test with severity level 1 to FN 942017-4 and EN; 60068-2-6
Shock resistanceShock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Max. cable length30 m inputs
LABS (PWIS) conformityVDMA24364 zone III
CE mark (see declaration of conformity)To EU EMC Directive; In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC; To UK RoHS instructions
KC markKC-EMV
ApprovalRCM; c UL us - Listed (Oil)
Certificate issuing authorityUL E239998
Note on materialsRoHS compliant
Material housingPA
Diagnostics via LEDErrors per module; Status per channel
Diagnostics via busShort circuit/overload in sensor supply
Max. address volume, inputs2 Byte
Module parametersShort circuit diagnostics for sensor supply; Input debounce time; Signal extension time; Behaviour after short circuit/overload
Channel parametersSignal extension
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors±25%
Intrinsic current consumption at nominal electronics/sensor voltageTypically 15 mA
Reverse polarity protection24 V sensor supply against 0 V sensor supply
Electrical connection input, functionDigital input
Electrical connection input, connection type8x terminal strip
Electrical connection input, connector systemSpring-loaded terminal
Electrical connection input, number of connections/cores6
Electrical connection for input, conductor cross section0.2 mm²...1.5 mm²
Electrical connection for input, note on conductor cross section0.2 - 2.5 mm² for flexible conductors without wire ferrule
Number of inputs16
Characteristic for inputsTo IEC 61131-2, type 3
Switching levelSignal 0: <= 5 V; Signal 1: ≥ 11 V
Switching logic for inputsPNP (positive switching); 2-wire sensors to IEC 61131-2; 3-wire sensors to IEC 61131-2
Input debounce time0.1 ms; 3 ms; 10 ms; 20 ms
Maximum total input current per module1.8 A
Isolation channel - channelNo
Isolation channel - internal busNo
Fuse protection (short circuit)Internal electronic fuse per module
Dimensions L x W x H (cm)7.66 x 1.89 x 12.43

Industrial Applications

1. Cylinder Position Feedback for an Assembly Sequence

A CPX-E-controlled assembly machine needs position signals from several pneumatic cylinders. The input module accepts compatible two- and three-wire PNP sensors through sixteen digital channels, using two bytes of input address space. Individual channel-state LEDs expose the received signals locally, while eight spring-terminal strips provide the field wiring points for the sensor circuits.

Problem Solved

Sixteen digital inputs collect the position conditions required by the machine sequence, and local LEDs help correlate the controller input state with the connected sensor circuit.

16 PNP inputs 2-wire/3-wire sensors Channel LEDs

2. Debounce Filtering for Discrete Machine Signals

A machine input can change briefly during a mechanical transition or sensor-edge disturbance, producing unwanted rapid state changes. The CPX-E-16DI offers selectable debounce times of 0.1, 3, 10 and 20 ms, allowing input evaluation to be configured for that signal behaviour. Its type 3 switching levels define the electrical high and low conditions accepted by the module.

Problem Solved

Configurable debounce adds a defined input qualification interval, helping the control system reject brief state changes while retaining a documented choice of response times.

0.1/3/10/20 ms debounce IEC type 3

3. Extending Short Sensor Events for Sequence Evaluation

A handling machine produces brief discrete sensor events that need to remain available long enough for the control sequence to evaluate them. The module provides a signal-extension time parameter and a per-channel signal-extension setting. Combined with its sixteen PNP inputs and 30 m maximum input cable length, these functions support configuring the acquisition of short-duration machine events.

Problem Solved

Signal extension can preserve a received event for the configured evaluation interval, helping the controller observe a brief input without assigning an unsupported maximum counting frequency.

Signal extension 16 digital inputs 30 m input cables