$ 133.40
| input | |
| type of the power supply network | 1-phase AC or DC |
| supply voltage at AC | |
| ● minimum rated value | 100 V |
| ● maximum rated value | 240 V |
| ● initial value | 85 V |
| ● full-scale value | 264 V |
| input voltage at DC | 110 … 300 V |
| wide range input | Yes |
| overvoltage overload capability | 300 V AC for 1 s |
| buffering time for rated value of the output current in the event of power failure minimum |
40 ms |
| operating condition of the mains buffering | at Vin = 187 V |
| line frequency | 50/60 Hz |
| line frequency | 47 … 63 Hz |
| input current | |
| ● at rated input voltage 120 V | 0.71 A |
| ● at rated input voltage 230 V | 0.37 A |
| current limitation of inrush current at 25 °C maximum | 50 A |
| I2t value maximum | 3 A²·s |
| fuse protection type | internal |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
| output | |
| voltage curve at output | Controlled, isolated DC voltage |
| output voltage at DC rated value | 5 V |
| output voltage | |
| ● at output 1 at DC rated value | 5 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 4.6 … 5.4 V |
| relative overall tolerance of the voltage | 3 % |
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % |
| ● on slow fluctuation of ohm loading | 0.1 % |
| residual ripple | |
| ● maximum | 100 mV |
| ● typical | 30 mV |
| voltage peak | |
| ● maximum | 100 mV |
| ● typical | 50 mV |
| display version for normal operation | Green LED for output voltage OK |
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| response delay maximum | 0.5 s |
| voltage increase time of the output voltage | |
| ● typical | 100 ms |
| output current | |
| ● rated value | 6.3 A |
| ● rated range | 0 … 6.3 A; +55 … +70 °C: Derating 2%/K |
| supplied active power typical | 31.5 W |
| bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing the power |
2 |
| efficiency | |
| efficiency in percent | 79.8 % |
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical |
8 W |
| ● during no-load operation maximum | 0.3 W |
| closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.2 % |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
7 % |
| setting time | |
| ● load step 10 to 90% typical | 1 ms |
| ● load step 90 to 10% typical | 1 ms |
| protection and monitoring | |
| design of the overvoltage protection | Yes, according to EN 60950-1 |
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Constant current characteristic |
| ● typical | 8.2 A |
| overcurrent overload capability | |
| ● when switching on | 150% Iout rated typ. 200 ms |
| ● in normal operation | overload capability 150% Iout rated typ. 200 ms |
| enduring short circuit current RMS value | |
| ● maximum | 8.2 A |
| measuring point for output current | Yes; 50 mV =^ 6.3 A |
| safety | |
| galvanic isolation between input and output | Yes |
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
| operating resource protection class | Class II (without protective conductor) |
| protection class IP | IP20 |
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B |
| ● for mains harmonics limitation | not applicable |
| ● for interference immunity | EN 61000-6-2 |
| standards, specifications, approvals | |
| certificate of suitability | |
| ● CE marking | Yes |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
| ● EAC approval | Yes |
| ● NEC Class 2 | No |
| ● SEMI F47 | Yes |
| type of certification | |
| ● CB-certificate | Yes |
| MTBF at 40 °C | 2 654 280 h |
| standards, specifications, approvals hazardous environments | |
| certificate of suitability | |
| ● IECEx | No |
| ● ATEX | No |
| ● ULhazloc approval | No |
| ● cCSAus, Class 1, Division 2 | No |
| ● FM registration | No |
| standards, specifications, approvals marine classification | |
| shipbuilding approval | Yes |
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| ● French marine classification society (BV) | Yes |
| ● Det Norske Veritas (DNV) | Yes |
| ● Lloyds Register of Shipping (LRS) | Yes |
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes |
| global warming potential [CO2 eq] | |
| ● total | 222.9 kg |
| ● during manufacturing | 3.8 kg |
| ● during operation | 218.9 kg |
| ● after end of life | 0.14 kg |
| ambient conditions | |
| ambient temperature | |
| ● during operation | -25 … +70; with natural convection |
| ● during transport | -40 … +85 |
| ● during storage | -40 … +85 |
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
| connection method | |
| type of electrical connection | screw terminal |
| ● at input | L, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely stranded |
| ● at output | +, -: 1 screw terminal each for 0.5 … 2.5 mm² |
| ● for auxiliary contacts | – |
| mechanical data | |
| width × height × depth of the enclosure | 54 × 90 × 53 mm |
| installation width × mounting height | 54 mm × 130 mm |
| required spacing | |
| ● top | 20 mm |
| ● bottom | 20 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positions |
| ● DIN-rail mounting | Yes |
| ● S7 rail mounting | No |
| ● wall mounting | Yes |
| housing can be lined up | Yes |
| net weight | 0.2 kg |