Contact Us:
sales@inosaki.com

MACX MCR-EX-SL-RPSSI-I – 2865340 – Power/input Signal Conditioner – Phoenix Contact Signal Conditioners And Measuring Transducers

$ 197.80

Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.

Commercial Data

Item number 2865340
Packing unit 1 pc
Minimum order quantity 1 pc
Product key DK1211
Catalog page Page 142 (C-5-2019)
GTIN 4046356160353
Weight per piece (including packing) 182.5 g
Weight per piece (excluding packing) 160 g
Customs tariff number 85437090
Country of origin DE

Product Properties

Product type Repeater power supply
Product family MACX Analog
Application Analog IN
No. of channels 1
Type Ex i signal conditioners with SIL functional safety

Electrical Properties

Electrical isolation 3-way isolation
Electrical isolation between input and output yes
Maximum power dissipation for nominal condition 0.95 W (20 mA, 250 Ω)
Signal transmission behavior In = Out
Step response (10-90%) < 200 µs (for jump 4 mA … 20 mA, load 600 Ω)
< 600 µs (for jump 0 mA … 20 mA, load 600 Ω)
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.004 %/K
Maximum transmission error < 0.1 % (of final value 20 mA)
Transmission error, typical < 0.05 % (of final value 20 mA)
Reverse polarity protection yes
Electrical isolation
Test voltage 2.5 kV AC (50 Hz, 60 s)
Overvoltage category II
Pollution degree 2
Electrical isolation Input/output/power supply IEC/EN 61010-1
Standards/regulations IEC/EN 61010-1
Rated insulation voltage 300 Vrms
Insulation Safe isolation
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulations IEC/EN 60079-11
Rated insulation voltage 265 Vrms
Electrical isolation Input/power supply IEC/EN 60079-11
Standards/regulations IEC/EN 60079-11
Rated insulation voltage 265 Vrms
Electrical isolation Output/supply IEC/EN 60079-7
Standards/regulations IEC/EN 60079-7
Rated insulation voltage 265 Vrms
Supply
Designation Repeater power supply operation
Nominal supply voltage 24 V DC -20 % … +25 %
Supply voltage range 19.2 V DC … 30 V DC
Max. current consumption < 76 mA (24 V DC / 20 mA / 1000 Ω)
< 55 mA (24 V DC / 20 mA / 250 Ω)
Power dissipation < 1.1 W (24 V DC / 20 mA / 1000 Ω)
< 0.95 W (24 V DC / 20 mA / 250 Ω)
< 1.2 W (24 V DC / 20 mA / 0 Ω)
Power consumption (Output active) < 1.8 W (20 mA / 1000 Ω)
< 1.3 W (20 mA / 250 Ω)
Supply
Designation Signal conditioner operation
Nominal supply voltage 24 V DC -20 % … +25 %
Supply voltage range 19.2 V DC … 30 V DC
Max. current consumption < 44 mA (24 V DC / 20 mA / 1000 Ω)
< 27 mA (24 V DC / 20 mA / 250 Ω)
Power dissipation < 0.75 W (24 V DC / 20 mA / 1000 Ω)
< 0.65 W (24 V DC / 20 mA / 250 Ω)
< 0.95 W (24 V DC / 20 mA / 0 Ω)

Input Data

Signal: Repeater power supply operation
Description of the input Active current input, intrinsically safe
Number of inputs 1
Input signal Current
Current input signal 4 mA … 20 mA
Current limitation 25 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Polarization and surge protection Yes
Underload/overload signal range 0 mA … 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Description of the input Passive current input, intrinsically safe
Current input signal 0 mA … 20 mA
4 mA … 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range 0 mA … 24 mA (Extended transmission range for diagnostics)

Output Data

Signal: Repeater power supply operation
Output description Current output (active and passive)
Number of outputs 1
Current output signal 4 mA … 20 mA (active)
4 mA … 20 mA (14 … 26 V ext. source voltage)
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Underload/overload signal range 0 mA … 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Output description Current output (active and passive)
Current output signal 0 mA … 20 mA (active)
4 mA … 20 mA (active)
0 mA … 20 mA (14 … 26 V ext. source voltage)
4 mA … 20 mA (14 … 26 V ext. source voltage)
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Underload/overload signal range 0 mA … 24 mA (Extended transmission range for diagnostics)

Connection Data

Connection method Screw connection
Stripping length 7 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² … 2.5 mm²
Conductor cross section flexible 0.2 mm² … 2.5 mm²
Conductor cross section AWG 24 … 14
Tightening torque 0.5 Nm … 0.6 Nm
Test socket
Max. diameter 2 mm

Ex Data

Ex installation (EPL) Gc
Div. 2
Ex i circuits (EPL) Ga
Da
Ma
Div. 1
Safety data: Repeater power supply operation
Max. output voltage Uo 25.2 V
Max. output current Io 93 mA
Max. output power Po 587 mW
Safety-related maximum voltage Um 253 V AC
125 V DC
I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 40 mH / 4.8 µF
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 26 mH / 2.9 µF
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 14 mH / 820 nF
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 3 mH / 107 nF
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co 26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF
IIB/III (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co 16 mH / 370 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co 2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF
I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co 37 mH / 0.54 µF, 0.35 mH / 1 µF, 0.009 mH / 2.9 µF, 0.001 mH / 4.15 µF
Safety data: Signal conditioner operation
Input voltage Ui ≤ 30 V
Input current Ii ≤ 150 mA
Max. internal inductance Li negligible
Max. internal capacitance Ci negligible
Safety-related maximum voltage Um 253 V AC
125 V DC

Interfaces

Data communication (bypass)
HART function Yes
Protocols supported HART-transparent

Signaling

Status display Green LED (supply voltage)

Dimensions

Width 12.5 mm
Height 112.5 mm
Depth 113.7 mm
Depth NS 35/7,5 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material Specifications

Color gray (RAL 7042)
Flammability rating according to UL 94 V0 (Housing)
Housing material PA 6.6-FR

Environmental And Real-life Conditions

Ambient conditions
Degree of protection IP20 (not assessed by UL)
Ambient temperature (operation) -40 °C … 60 °C (Any mounting position)
-40 °C … 70 °C (Derating)
Ambient temperature (storage/transport) -40 °C … 80 °C
Permissible humidity (operation) 10 % … 95 % (non-condensing)
Altitude range (≤ 2000 m)
Altitude ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.)
Ambient temperature (operation) -40 °C … 60 °C
-40 °C … 70 °C (Derating)
Rated insulation voltage 375 VPP (Power supply, input / output)
Altitude range (≤ 3000 m)
Height range > 2000 m … 3000 m
Ambient temperature (operation) -40 °C … 54 °C
-40 °C … 63 °C (Derating)
Rated insulation voltage 190 V AC (Power supply, input / output)
110 V DC (Power supply, input / output)
Altitude range (≤ 4000 m)
Height range > 3000 m … 4000 m
Ambient temperature (operation) -40 °C … 48 °C
-40 °C … 56 °C (Derating)
Rated insulation voltage 60 V AC/DC (Power supply, input / output)
Altitude range (≤ 5000 m)
Height range > 4000 m … 5000 m
Ambient temperature (operation) -40 °C … 42 °C
-40 °C … 49 °C (Derating)
Rated insulation voltage 60 V AC/DC (Power supply, input / output)

Approvals

CE
Certificate CE-compliant
Note and EN 61326
ATEX
Identification  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
Certificate BVS 08 ATEX E 054X
IECEx
Identification [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
Certificate IECEx BVS 08.0016X
CCC / China-Ex
Identification [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
Certificate 2022122316115973
UL, USA/Canada
Identification UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Div. 2, Groups IIC, IIB, IIA T4
Associated apparatus for use in Class I, Division 1, Groups A,B,C,D
Associated apparatus for use in Class II, Div.1 Groups E,F,G
Associated apparatus for use in Class III, Division 1
Associated apparatus for use in Class I, Zone 0,1,2, Groups IIC,IIB,IIA
Certificate , C.D.-No 83104549
UL, USA/Canada
Identification UL 61010 Listed
Class I Div 2; IS for Class I, II, III Div 1
Certificate , C.D.-No 83104549
Shipbuilding approval
Certificate DNV GL TAA000020C
Safety Integrity Level (SIL, IEC 61508)
Identification 2
Certificate IN-AT-AS-MRL-2300149
Systematic Capability
Identification 3
KC-s
Identification [Ex ia] IIC/IIB
Certificate 17-KA4BO-0400X
INMETRO
Identification [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
Certificate DNV 18.0136 X
Shipbuilding data
Temperature B
Humidity B
Vibration A
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

EMC Data

Electromagnetic compatibility Conformance with EMC directive
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Noise emission
Standards/regulations EN 61000-6-4
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 1 %
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 1 %
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 1 %

Standards And Regulations

Electrical isolation 3-way isolation
GB Standard
Standards/regulations GB/T 3836.1
GB/T 3836.3
GB/T 3836.4

Mounting

Mounting type DIN rail mounting

Additional information

Weight 0.1825 kg
Dimensions 11.45 × 1.25 × 11.25 cm

Related Products

SCHNEIDER_Terminal Block for 35 MM Rail (For LRD01…35C)
Phoenix_Contact_Plug-in_Bridge_FBS 5-5 BU_3036903
Panasonic_RF-210
BJ10M-TDT
Festo_Vacuum suction cups_ESS-10-SN_189284
SICK_Inductive Proximity Sensors_IME12-04NPSZC0S
Select your currency