Inosaki – Your Trusted Phoenix Contact Distributor
Inosaki proudly stands as one of the largest distributors of Phoenix Contact products, offering a comprehensive range of terminal blocks, interface modules, power supplies, and relays.

Our Best-Selling Terminal Blocks: Feed-Through, Fuse Modular, Spring Cage, Double Level, Multi-Level

Series Models: PT Series, ST Series, TB Series, UT Series, and UK Series, PTV Series, UKH Series, Micro Series.

Reliable Power Supply Solutions

Discover industry-leading Phoenix Contact power supplies, such as:

  • QUINT Power – Premium performance for critical systems
  • STEP Power – Compact design for space-saving applications
  • Trio Power – Rugged and reliable for industrial needs
  • UNO Power – Cost-effective and efficient

Get Your Phoenix Contact Catalog Today
Need detailed product information? Contact us at sales@inosaki.com to request your Phoenix Contact catalog.

Feed-through terminal block, nom. voltage: 500 V, nominal current: 17.5 A, connection method: Push-in connection, number of connections: 2, cross section: 0.14 mm² – 1.5 mm², AWG: 26 – 14, width: 3.5 mm, height: 30.5 mm, color: gray, mounting type: NS 35/7,5, NS 35/15

General

Article Number 3208100
Number of levels 1
Number of connections 2
Potentials 1
Nominal cross section 1.5 mm²
Color gray
Insulating material PA
Flammability rating according to UL 94 V0
Area of application Railway industry
Machine building
Plant engineering
Mounting type NS 35/7,5
Rated surge voltage 6 kV
Degree of pollution 3
Overvoltage category III
Insulating material group I
Maximum load current 17.5 A
Nominal current IN 17.5 A
Nominal voltage UN 500 V
Open side panel Yes
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Result of surge voltage test Test passed
Result of power-frequency withstand voltage test Test passed
Power frequency withstand voltage setpoint 1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
Result of flexion and pull-out test Test passed
Bending test rotation speed 10 rpm
Bending test turns 135
Bending test conductor cross section/weight 0.14 mm² / 0.2 kg
1.5 mm² / 0.4 kg
Tensile test result Test passed
Result of tight fit on support Test passed
Tight fit on carrier NS 35
Setpoint 1 N
Result of voltage-drop test Test passed
Result of temperature-rise test Test passed
Requirement temperature-rise test Increase in temperature ≤ 45 K
Short circuit stability result Test passed
Conductor cross section short circuit testing 1.5 mm²
Short-time current 0.18 kA
Result of thermal test Test passed
Proof of thermal characteristics (needle flame) effective duration 30 s
Result of aging test Test passed
Oscillation, broadband noise test result Test passed
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
Test spectrum Service life test category 2, bogie-mounted
Test frequency f1 = 5 Hz to f2 = 250 Hz
ASD level 6.12 (m/s²)²/Hz
Acceleration 3.12g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Shock test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2018-05
Shock form Half-sine
Acceleration 30g
Shock duration 18 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Static insulating material application in cold -60 °C
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 – HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 – HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 – HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 – HL 3

 

Dimensions

Width 3.5 mm
End cover width 2.2 mm
Length 45 mm
Height 30.5 mm
Height NS 35/7,5 32 mm
Height NS 35/15 39.5 mm

Connection data

Connection 1 level
Connection method Push-in connection
Stripping length 8 mm … 10 mm
Connection in acc. with standard IEC 60947-7-1
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 14
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 1.5 mm²
Min. AWG conductor cross section, flexible 26
Max. AWG conductor cross section, flexible 14
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 1 mm² Using the AI-S 1-8 TQ ferrule, Order No. 1200293, is recommended
Connection cross sections directly pluggable 0.25 mm² 1.5 mm²
Conductor cross section solid min. 0.25 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.34 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.34 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 1 mm²
Internal cylindrical gage A1 / B1

Ambient conditions

Operating temperature -60 °C … 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport) -25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport) 30 % … 70 %
Ambient temperature (assembly) -5 °C … 70 °C
Ambient temperature (actuation) -5 °C … 70 °C

Standards and Regulations

Connection in acc. with standard CSA
IEC 60947-7-1
Flammability rating according to UL 94 V0

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Additional information

Related Products

ST 4 - Feed-through terminal block - 3031364(50 pcs) -Phoenix Contact
M8
IDS_camera_GV-5991SE_1
IDS_Power Supply
SICK_sensor_Photoelectric_sensor_V18 Laser_VSE18L-4N324
IDS_Camera_uEye+_SE_BoardLevel_C_Mount_1