Contact Us:
sales@inosaki.com

QUINT4-PS/12-24DC/24DC/1.3/SC – 1066703 – Phoenix Contact DC/DC Converters

$ 132.00

SKU Phoenix Contact 1066703 Category

Inosaki – Your Trusted Phoenix Contact Distributor
Inosaki proudly stands as one of the largest distributors of Phoenix Contact products, offering a comprehensive range of terminal blocksinterface modulespower supplies, and relays.

Our Best-Selling Terminal Blocks: Feed-Through, Fuse Modular, Spring Cage, Double Level, Multi-Level

Series Models: PT SeriesST SeriesTB SeriesUT Series, and UK SeriesPTV SeriesUKH SeriesMicro Series.

Reliable Power Supply Solutions

Discover industry-leading Phoenix Contact power supplies, such as:

  • QUINT Power – Premium performance for critical systems
  • STEP Power – Compact design for space-saving applications
  • Trio Power – Rugged and reliable for industrial needs
  • UNO Power – Cost-effective and efficient

Get Your Phoenix Contact Catalog Today
Need detailed product information? Contact us at sales@inosaki.com to request your Phoenix Contact catalog.

Product Description

MINI DC/DC converter for MCR technology.
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.

 

Commercial Data

Item number 1066703
Packing unit 1 pc
Minimum order quantity 1 pc
Product key CMDI43
GTIN 4055626733692
Weight per piece (including packing) 227.6 g
Weight per piece (excluding packing) 169 g
Customs tariff number 85044095
Country of origin CN

Product Properties

Product type DC/DC converters
Product family QUINT POWER
MTBF (IEC 61709, SN 29500) > 1999348 h (25 °C)
> 1120490 h (40 °C)
> 471066 h (60 °C)
Insulation characteristics
Protection class II
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 0.65 A
Temperature 40 °C
Time 242000 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 1.3 A
Temperature 40 °C
Time 160000 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 1.3 A
Temperature 30 °C
Time 320000 h
Additional text 24 V DC

Electrical Properties

Number of phases 1.00
Insulation voltage input/output 2.6 kV DC (type test)
1.2 kV DC (routine test)
Switching frequency 130.00 kHz … 130.00 kHz (Auxiliary converter stage)
70.00 kHz … 250.00 kHz (Main converter stage)

Input Data

Nominal input voltage range 12 V DC … 24 V DC
Input voltage range 12 V DC … 24 V DC -25 % … +33 % (SELV)
Wide-range input yes
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 1.6 A
Inrush current integral (I2t) typ. 0.1 A2s
Inrush current limitation typ. 1.6 A
Mains buffering time typ. 19 ms (24 V DC)
Current consumption typ. 3.75 A (12 V DC)
typ. 1.85 A (24 V DC)
Typical response time 700 ms (from SLEEP MODE)
Switch-on time < 1 s
Input fuse 15 A (fast blow, internal)
Recommended breaker for input protection 10 A … 16 A (Characteristic B, C, D, K or comparable)

Output Data

Efficiency typ. 91.7 % (24 V DC)
Output characteristic U/I Advanced
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC … 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 1.3 A
Static Boost (IStat.Boost) 1.625 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 2.6 A (≤ 60 °C (4.9 s))
Short-circuit-proof yes
No-load proof yes
Derating > 60 °C (2.5%/K of POut nom.)
Output power (PN) 30 W
Output power (PStat. Boost) 38 W
Output power (PDyn. Boost) 60 W
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) < 32 V DC
Residual ripple < 20 mVPP
Control deviation static < 1 % (change in load, static 10 % … 90 %)
Control deviation dynamic < 1 % (change in load, static 10 % … 90 %)
Control deviation Input voltage change < 1 % (change in load, static 10 % … 90 %)
Rise time < 1 s (UOUT (10 % … 90 %))
Connection in series yes
Maximum no-load power dissipation < 1.3 W
Power loss nominal load max. < 8 W
Connection in parallel yes, for redundancy and increased capacity

Connection Data

Input
Position 1.x
Conductor connection
Connection method Screw connection
rigid 0.5 mm² … 2.5 mm²
flexible 0.5 mm² … 2.5 mm²
flexible with ferrule without plastic sleeve 0.5 mm² … 2.5 mm²
flexible with ferrule with plastic sleeve 0.5 mm² … 2.5 mm²
rigid (AWG) 22 … 14
Stripping length 8 mm
Tightening torque 0.5 Nm … 0.6 Nm
Drive form screw head Slotted L
Output
Position 2.x
Conductor connection
Connection method Screw connection
rigid 0.2 mm² … 2.5 mm²
flexible 0.25 mm² … 2.5 mm²
flexible with ferrule without plastic sleeve 0.25 mm² … 2.5 mm²
flexible with ferrule with plastic sleeve 0.25 mm² … 2.5 mm²
rigid (AWG) 24 … 14
Stripping length 8 mm
Tightening torque 0.5 Nm … 0.6 Nm
Drive form screw head Slotted L
Signal
Position 3.x
Conductor connection
Connection method Screw connection
rigid 0.14 mm² … 2.5 mm²
flexible 0.14 mm² … 2.5 mm²
flexible with ferrule without plastic sleeve 0.25 mm² … 2.5 mm²
flexible with ferrule with plastic sleeve 0.25 mm² … 2.5 mm²
rigid (AWG) 26 … 14
Stripping length 8 mm
Tightening torque 0.5 Nm … 0.6 Nm
Drive form screw head Slotted L

Signaling

LED signaling
Signal threshold > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
> 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)
Signal output Configurable
Digital 0 V DC
24 V DC
22 mA
Default 24 V DC
22 mA
24 V DC for UOut > 0.9 x USet

Dimension

Item dimensions
Width 22.5 mm
Height 99 mm
Depth 90 mm
Installation dimensions
Installation distance right/left (active) 15 mm / 15 mm (POut ≥50% )
Installation distance right/left (passive) 5 mm / 5 mm (POut ≥50% )
Installation distance right/left (active, passive) 0 mm / 0 mm (POut ≤50 %)
Installation distance top/bottom (active) 30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (passive) 30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (active, passive) 30 mm / 30 mm (POut ≤50 %)

Material Specifications

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Plastic
Type of housing Polycarbonate (PC), UL 94 V0

Environmental and real-life conditions 

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, ±2.5 mm amplitude; 15 Hz … 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)
Temp code T4 (-25 … +70 °C; > 60 °C, Derating: 2,5 %/K)

Standards And Regulations

Overvoltage category
EN 61010-1 II (≤ 5000 m)
Safety for measurement, control, and laboratory equipment
Standard designation Electrical safety (of control and regulation devices)
Standards/specifications IEC 61010-1
Protective extra-low voltage
Standard designation Protective extra-low voltage
Standards/specifications IEC 61010-1 (SELV)
Mains voltage dips
Standard designation Mains variation/undervoltage
Standards/specifications EN 61000-4-29

Approvals

UL
Identification UL Listed UL 61010-1
UL
Identification UL Listed UL 61010-2-201
UL
Identification UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CSA
Identification CAN/CSA C22.2 No. 61010-1-12
CSA
Identification CAN/CSA C22.2 No. 61010-2-201:18
SIQ
Identification CB scheme (IEC 61010-1, IEC 61010-2-201)
Shipbuilding
Identification DNV GL

EMC Data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant EN 61850-3
EN 61000-6-5
Conducted noise emission
Standards/regulations EN 55016
EN 61000-6-3 (Class B)
Noise emission
Standards/regulations Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission
Standards/regulations EN 55016
EN 61000-6-3 (Class B)
DNV GL conducted noise emissions
DNV Class B
Additional text Bridge and deck area
DNV GL noise radiation
DNV Class B
Additional text Bridge and deck area
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 3)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz … 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz … 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 4 – asymmetrical)
Output 2 kV (Test Level 4 – asymmetrical)
Signal 2 kV (Test Level 4 – asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Surge voltage load (surge)
Input 0.5 kV (Test Level 3 – symmetrical)
1 kV (Test Level 3 – asymmetrical)
Output 0.5 kV (Test Level 2 – symmetrical)
1 kV (Test Level 1 – asymmetrical)
Signal 0.5 kV (Test Level 2 – symmetrical)
1 kV (Test Level 1 – asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Input/output/signal asymmetrical
Frequency range 0.15 MHz … 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.67 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz … 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Voltage dips
Standards/regulations EN 61000-4-29
Voltage 24 V DC
Voltage dip 70 %
Number of periods 0.5 / 1 / 25 periods
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 5 / 10 / 50 periods
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Number of periods 0.5 / 1 / 5 / 50 periods
Time 50 ms
Additional text Test Level 2
Comments Criterion B
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 3)
Voltage 10 V 1 V (Permanent)
Test level 2 150 Hz 1.5 kHz (Test Level 3)
Voltage 1 V
Test level 3 1.5 kHz 15 kHz (Test Level 3)
Voltage 1 V 10 V
Test level 4 15 kHz 150 kHz (Test Level 3)
Voltage 10 V
Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage 10 V (Permanent)
Test level 6 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
Voltage 100 V (1 s)
Comments Criterion A
Alternating component of direct voltage
Standards/regulations EN 61000-4-17
Alternating component 10 % (UN)
Frequency 50 Hz
100 Hz
150 Hz
300 Hz
Comments Criterion A
Attenuated oscillating wave
Standards/regulations EN 61000-4-18
Input, output (test level 1) 1 MHz (Test Level 2 – symmetrical)
Voltage 0.5 kV
Input, output (test level 2) 1 MHz (Test Level 2 – asymmetrical)
Voltage 1 kV
Signals (test level 1) 1 MHz (Test Level 2 – symmetrical)
Voltage 0.5 kV
Signals (test level 2) 1 MHz (Test Level 2 – asymmetrical)
Voltage 1 kV
Comments Criterion A
Attenuated oscillating magnetic field
Standards/regulations EN 61000-4-10
Test field strength 100 A/m
Test level 1 100 kHz
Test field strength 100 A/m
Test level 2 1 MHz
Comments Criterion A
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Mounting

Mounting type DIN rail mounting
Assembly note alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
With protective coating no

Additional information

Weight 0.2276 kg
Dimensions 9 × 2.25 × 9.9 cm

Related Products

BX700-DFR
QS18VN6LLPQ
Festo_Couplings_KS2-CK-3_4091_1
Festo_Shut off valves pneumatic_HB-1-8-QS-6_153449
Mitutoyo_Dial Indicator Thickness Gauges_7323A
SICK_sensor_Distance sensor_UM30_UM30-213111
Select your currency