USD 1,086.54 – USD 1,328.34Price range: USD 1,086.54 through USD 1,328.34
The SIRIUS modular system with its components for the switching, starting, protection and monitoring of motors and industrial systems stands for the fast, flexible and space-saving construction of control cabinets.
| Article Number | 3RT1054-6AP36
3RT1054-1AP36 |
| product brand name | SIRIUS |
| product designation | Power contactor |
| product type designation | 3RT1 |
| General technical data | |
| size of contactor | S6 |
| product extension | |
| ● function module for communication | No |
| ● auxiliary switch | Yes |
| power loss [W] for rated value of the current | |
| ● at AC in hot operating state | 21 W |
| ● at AC in hot operating state per pole | 7 W |
| ● without load current share typical | 5.2 W |
| insulation voltage | |
| ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| ● of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| surge voltage resistance | |
| ● of main circuit rated value | 8 kV |
| ● of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation between | 690 V |
| coil and main contacts according to EN 60947-1 | |
| shock resistance at rectangular impulse | |
| ● at AC | 8,5g / 5 ms, 4,2g / 10 ms |
| ● at DC | 8,5g / 5 ms, 4,2g / 10 ms |
| shock resistance with sine pulse | |
| ● at AC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| ● at DC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| mechanical service life (switching cycles) | |
| ● of contactor typical | 10 000 000 |
| ● of the contactor with added electronically optimized | 5 000 000 |
| auxiliary switch block typical | |
| ● of the contactor with added auxiliary switch block | 10 000 000 |
| typical | |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (Date) | 5/1/2012 |
| Ambient conditions | |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -25 … +60 °C |
| ● during storage | -55 … +80 °C |
| relative humidity minimum | 10% |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95% |
| Article Number | 3RT1055-6AP36 |
| product brand name | SIRIUS |
| product designation | Power contactor |
| product type designation | 3RT1 |
| General technical data | |
| size of contactor | S6 |
| product extension | |
| ● function module for communication | No |
| ● auxiliary switch | Yes |
| power loss [W] for rated value of the current | |
| ● at AC in hot operating state | 21 W |
| ● at AC in hot operating state per pole | 7 W |
| ● without load current share typical | 5.2 W |
| insulation voltage | |
| ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| ● of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| surge voltage resistance | |
| ● of main circuit rated value | 8 kV |
| ● of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation between | 690 V |
| coil and main contacts according to EN 60947-1 | |
| shock resistance at rectangular impulse | |
| ● at AC | 8,5g / 5 ms, 4,2g / 10 ms |
| ● at DC | 8,5g / 5 ms, 4,2g / 10 ms |
| shock resistance with sine pulse | |
| ● at AC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| ● at DC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| mechanical service life (switching cycles) | |
| ● of contactor typical | 10 000 000 |
| ● of the contactor with added electronically optimized | 5 000 000 |
| auxiliary switch block typical | 10 000 000 |
| ● of the contactor with added auxiliary switch block | Q |
| typical | |
| reference code according to IEC 81346-2 | |
| Substance Prohibitance (Date) | 5/1/2012 |
| Ambient conditions | |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -25 … +60 °C |
| ● during storage | -55 … +80 °C |
| relative humidity minimum | 10% |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95% |