Sale!

Festo 8001220 Pressure Sensor, 0–10 bar, DIN Rail, IO-Link

Original price was: USD 180.18.Current price is: USD 155.22.

Illuminated LCD sensor with switchable PNP/NPN outputs, configurable voltage/current output, four-pin M12 connector and IP65/IP67 protection.

SKU Festo-8001220 Category
Festo Pressure Sensors And Vacuum Sensors

Festo SPAU-P10R-H-G18FD-L-PNLK-PNVBA-M12U Pressure Sensor

BrandFesto
Model IdentifierSPAU-P10R-H-G18FD-L-PNLK-PNVBA-M12U
Official Part Number8001220

Technical Overview

The Festo SPAU-P10R-H-G18FD-L-PNLK-PNVBA-M12U measures relative pressure from 0 to 10 bar through a G1/8 connection and mounts on a DIN rail. Its piezoresistive element and 12-bit ADC support two switchable PNP or NPN outputs, with selectable NO/NC behavior and programmable switching functions. Analogue output options are 0–10 V, 1–5 V or 4–20 mA, while IO-Link Device V1.1 supplies pressure and binary monitoring data over COM2. An illuminated LCD displays pressure in eight selectable units, with setup through buttons, teach-in or IO-Link. The 70 g sensor operates from 20–30 V DC through a four-pin A-coded M12 plug and has IP65/IP67 protection.

0–10 bar relative-pressure sensor with G1/8 thread, illuminated LCD, switchable PNP/NPN and analogue outputs, IO-Link and four-pin M12 connection.

Key Features

  • Piezoresistive 0–10 bar relative-pressure measurement
  • 12-bit ADC with ±1.5% FS accuracy and ±0.3% FS repetition accuracy
  • Two PNP or two NPN switching outputs, configurable NO/NC
  • Programmable switching function and adjustable threshold/hysteresis
  • Analogue options: 0–10 V, 1–5 V or 4–20 mA
  • IO-Link Device V1.1, COM2 and 3 ms minimum cycle time
  • IO-Link process data: 14-bit pressure value and two binary monitoring bits
  • Illuminated LCD with eight pressure-unit choices
  • G1/8 pneumatic connection, DIN-rail mounting, four-pin A-coded M12 plug and 20–30 V DC supply
  • 70 g product weight with IP65/IP67 protection

Combine local pressure display, programmable switching and analogue or IO-Link pressure reporting in a 0–10 bar G1/8 sensor.

Technical Specification Matrix

ParameterValue
ApprovalRCM; c UL us - Listed (Oil)
CE mark (see declaration of conformity)To EU EMC Directive; In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC; To UK RoHS instructions
KC markKC-EMV
Note on materialsRoHS compliant
Measured variableRelative pressure
Measurement methodPiezoresistive pressure sensor
Start value for pressure measuring range0 MPa; 0 bar; 0 psi
End value for pressure measuring range1 MPa; 10 bar; 145 psi
Overload pressure1.5 MPa; 15 bar; 217.5 psi
Operating mediumCompressed air to ISO 8573-1:2010 [7:4:4]; Inert gas
Note on operating and pilot mediumLubricated operation possible
Media temperature0 °C...50 °C
Ambient temperature0 °C...50 °C
Resolution ADC12 bit
Accuracy in ± % FS1.5 %FS
Repetition accuracy in ± %FS0.3 %FS
Temperature coefficient in ± %FS/K0.05 %FS/K
Switching output2 x PNP or 2 x NPN, switchable
Switching functionFreely programmable
Switching element functionNC or NO, switchable
Max. output current100 mA
Analogue output0 - 10 V; 4 - 20 mA; 1 - 5 V
Rise time3 ms
Max. load resistance current output500 Ohm
Min. load resistance voltage output10 kOhm
Short circuit current ratingYes
Overload protectionYes
ProtocolIO-Link®
IO-Link, Protocol versionDevice V 1.1
IO-Link, ProfileSmart sensor profile
IO-Link, Function classesBinary data channel (BDC); Process data variable (PDV); Identification; Diagnostics; Teach channel
IO-Link, communication modeCOM2 (38.4 kBaud)
IO-Link, SIO-Mode supportYes
IO-Link, Port classA
IO-Link, Process data length OUT0 bytes
IO-Link, Process data length IN2 bytes
IO-Link, Process data content IN14 bit PDV (pressure measurement value); 2 bit BDC (pressure monitoring)
IO-Link, Min. cycle time3 ms
IO-Link, Data storage required0.5 KB
Operational voltage range DC20 V...30 V
Reverse polarity protectionFor all electrical connections
Electrical connection 1, connection typePlug
Electrical connection 1, connector systemM12x1, A-coded to EN 61076-2-101
Electrical connection 1, number of connections/cores4
Electrical connection 1, type of mountingNot rotatable
Electrical connection 1, compatible type of mountingCompatible with rotatable screw-type lock
Type of mountingvia DIN rail
Mounting positionAny
Pneumatic connectionG1/8
Physical Weight (kg)0.07
Material in contact with the mediumFluoro rubber; Reinforced PA; High-alloy stainless steel
Display typeIlluminated LCD
Displayable unitsMPa; bar; inH2O; inHg; kPa; kgf/cm²; mmHg; psi
Setting optionsIO-Link®; Teach-in; Via display and buttons
Protection against tamperingIO-Link®; PIN code
Setting range threshold value0 %...100 %
Setting range hysteresis0 %...90 %
Degree of protectionIP65; IP67
Corrosion resistance class CRC2 - Moderate corrosion stress
LABS (PWIS) conformityVDMA24364-B1/B2-L

Industrial Applications

1. Pressure-Condition Monitoring for a Pneumatic Fixture

A fixture sequence needs a discrete indication that its monitored air pressure meets the selected operating condition. The sensor provides two switchable PNP or NPN outputs with programmable switching functions, NO/NC behavior and adjustable hysteresis. The 0–10 bar range and G1/8 connection characterize the pressure interface, while the illuminated display lets the operator observe the local value alongside the controller's binary monitoring signals.

Problem Solved

Programmable pressure switching turns the measured branch pressure into controller conditions for the fixture sequence, while the local display provides direct visibility of the monitored value.

0–10 bar Two switching outputs Adjustable hysteresis

2. Continuous Pressure Recording in a Test Station

A pneumatic test station needs a pressure value for recording or evaluating a process cycle rather than only a threshold event. The sensor offers selectable voltage or current output formats, including 4–20 mA, with a 3 ms rise time. The specified ±1.5% FS accuracy and ±0.3% FS repetition accuracy characterize the measurement, and the connected recorder determines how that signal is sampled and assessed.

Problem Solved

An analogue pressure signal supplies continuous measurement information to the test equipment, supporting cycle recording beyond the discrete result available from a switching threshold alone.

4–20 mA option 3 ms rise time ±1.5% FS accuracy

3. Remote Pressure-Sensor Setup and Diagnostics

A machine with distributed pressure points needs sensor parameter access and measurement data through its control network. IO-Link provides a pressure process value, two binary monitoring bits, diagnostics and a teach channel for this exact model. Configuration can be performed through IO-Link as well as the local display and buttons, with PIN-code and IO-Link tamper-protection options supporting management of the selected settings.

Problem Solved

IO-Link brings measurement, monitoring and configuration access to the controller interface, allowing the machine workflow to manage distributed sensor settings and diagnostics without relying solely on local button operation.

IO-Link V1.1 Pressure PDV + binary bits Teach and diagnostics
Select your currency