$ 6,599.85
| General information | |
| Product type designation | CPU 1516-3 PN/DP |
| HW functional status | FS04 |
| Firmware version ● FW update possible |
V4.0 Yes |
| Product function | |
| ● I&M data ● Isochronous mode ● SysLog |
Yes; I&M0 to I&M3 Yes; Distributed and central; with minimum OB 6x cycle of 375 µs (distributed) and 1 ms (central) Yes |
| Engineering with | |
| ● STEP 7 TIA Portal configurable/integrated from version | V20 (FW V4.0) / V18 (FW V3.0) or higher; configurable with older TIA Portal versions as 6ES7516-3AN02-0AB0 |
| Configuration control | |
| via dataset | Yes |
| Display | |
| Screen diagonal [cm] | 6.1 cm |
| Control elements | |
| Number of keys | 8 |
| Mode buttons | 2 |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Mains buffering | |
| ● Mains/voltage failure stored energy time ● Repeat rate, min. |
5ms 1/s |
| Input current | |
| Current consumption (rated value) | 0.69 A |
| Current consumption, max. | 1.08 A |
| Inrush current, max. | 1.15 A; Rated value |
| I²t | 0.6 A²·s |
| Power | |
| Infeed power to the backplane bus | 12 W |
| Power consumption from the backplane bus (balanced) | 6.7 W |
| Power loss | |
| Power loss, typ. | 4 W |
| Memory | |
| Number of slots for SIMATIC memory card | 1 |
| SIMATIC memory card required | Yes |
| Work memory | |
| ● integrated (for program) ● integrated (for data) |
2 Mbyte 7.5 Mbyte |
| Load memory | |
| ● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte |
| Backup | |
| ● maintenance-free | Yes |
| CPU processing times | |
| for bit operations, typ. | 6 ns |
| for word operations, typ. | 7 ns |
| for fixed point arithmetic, typ. | 9 ns |
| for floating point arithmetic, typ. | 37 ns |
| CPU-blocks | |
| Number of elements (total) | 8 000; Blocks (OB, FB, FC, DB) and UDTs |
| DB | |
| ● Number range
● Size, max. |
1 … 60 999; subdivided into: number range that can be used by the user: 1 … 59 999, and number range of DBs created via SFC 86: 60 000 … 60 999 7.5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB |
| FB | |
| ● Number range ● Size, max. |
0 … 65 535 1 Mbyte |
| FC | |
| ● Number range ● Size, max. |
0 … 65 535 1 Mbyte |
| OB | |
| ● Size, max. ● Number of free cycle OBs ● Number of time alarm OBs ● Number of delay alarm OBs ● Number of cyclic interrupt OBs ● Number of process alarm OBs ● Number of DPV1 alarm OBs ● Number of isochronous mode OBs ● Number of technology synchronous alarm OBs ● Number of startup OBs ● Number of asynchronous error OBs ● Number of synchronous error OBs ● Number of diagnostic alarm OBs |
1 Mbyte 100 20 20 20; With minimum OB 3x cycle of 250 µs 50 3 3 2 100 4 2 1 |
| Nesting depth | |
| ● per priority class | 24 |
| Counters, timers and their retentivity | |
| S7 counter | |
| ● Number | 2048 |
| Retentivity | |
| — adjustable | Yes |
| IEC counter | |
| ● Number | Any (only limited by the main memory) |
| Retentivity | |
| — adjustable | Yes |
| S7 times | |
| ● Number | 2048 |
| Retentivity | |
| — adjustable | Yes |
| IEC timer | |
| ● Number | Any (only limited by the main memory) |
| Retentivity | |
| — adjustable | Yes |
| Data areas and their retentivity | |
| Retentive data area (incl. timers, counters, flags), max. | 512 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 472 KB |
| Extended retentive data area (incl. timers, counters, flags), max. | 7.5 Mbyte; When using PS 6 0W 24/48/60 V DC HF |
| Flag | |
| ● Size, max. ● Number of clock memories |
16 kbyte 8; 8 clock memory bit, grouped into one clock memory byte |
| Data blocks | |
| ● Retentivity adjustable ● Retentivity preset |
Yes No |
| Local data | |
| ● per priority class, max. | 64 kbyte; max. 16 KB per block |
| Address area | |
| Number of IO modules | 8 192; max. number of modules / submodules |
| I/O address area | |
| ● Inputs ● Outputs |
32 kbyte; All inputs are in the process image 32 kbyte; All outputs are in the process image |
| per integrated IO subsystem | |
| — Inputs (volume) — Outputs (volume) |
8 kbyte 8 kbyte |
| per CM/CP | |
| — Inputs (volume) — Outputs (volume) |
8 kbyte 8 kbyte |
| Subprocess images | |
| ● Number of subprocess images, max. | 32 |
| Hardware configuration | |
| Number of distributed IO systems | 64; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) |
| Number of DP masters | |
| ● integrated ● Via CM |
1 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
| Number of IO Controllers | |
| ● integrated ● Via CM |
2 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
| Rack | |
| ● Modules per rack, max. ● Number of lines, max. |
32; CPU + 31 modules 1 |
| PtP CM | |
| ● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots |
| Time of day | |
| Clock | |
| ● Type ● Backup time ● Deviation per day, max. |
Hardware clock 6 wk; At 40 °C ambient temperature, typically 10 s; Typ.: 2 s |
| Operating hours counter | |
| ● Number | 16 |
| Clock synchronization | |
| ● supported ● to DP, master ● on DP, device ● in AS, master ● in AS, device ● on Ethernet via NTP |
Yes Yes Yes; via PROFIBUS CM / CP Yes Yes Yes |
| Interfaces | |
| Number of PROFINET interfaces | 2 |
| Number of PROFIBUS interfaces | 1 |
| 1. Interface | |
| Interface types | |
| ● RJ 45 (Ethernet) ● Number of ports ● integrated switch |
Yes;X1 2 Yes |
| Protocols | |
| ● IP protocol ● PROFINET IO Controller ● PROFINET IO Device ● SIMATIC communication ● Open IE communication ● Web server ● Media redundancy |
Yes; IPv4 Yes Yes Yes Yes; Optionally also encrypted Yes Yes |
| PROFINET IO Controller | |
| Services | |
| — Isochronous mode — Direct data exchange — IRT — PROFIenergy — Prioritized startup — Number of connectable IO Devices, max. — Of which IO devices with IRT, max. — PROFINET Security Class |
Yes Yes; Requirement: IRT and isochronous mode (MRPD optional) Yes Yes; per user program Yes; Max. 32 PROFINET devices 256; in total, up to 1024 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET 64 256 256 8; in total across all interfaces 8 |
| Update time for IRT | |
| — for send cycle of 250 µs
— for send cycle of 500 µs |
250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 375 µs of the isochronous OB is decisive 500 µs to 8 ms 1 ms to 16 ms 2 ms to 32 ms 4 ms to 64 ms Update time = set “odd” send clock (any multiple of 125 µs: 375 µs, 625 µs … 3 875 µs) |
| Update time for RT | |
| — for send cycle of 250 µs — for send cycle of 500 µs — for send cycle of 1 ms — for send cycle of 2 ms — for send cycle of 4 ms |
250 µs to 128 ms 500 µs to 256 ms 1 ms to 512 ms 2 ms to 512 ms 4 ms to 512 ms |
| PROFINET IO Device | |
| Services | |
| — Isochronous mode — IRT — PROFIenergy — Shared device — Number of IO Controllers with shared device, max. — activation/deactivation of I-devices — Asset management record — PROFINET Security Class |
No Yes Yes; per user program Yes 4 Yes; per user program Yes; per user program SNMP Configuration and DCP Read Only |
| 2. Interface | |
| Interface types | |
| ● RJ 45 (Ethernet) ● Number of ports ● integrated switch |
Yes; X2 1 No |
| Protocols | |
| ● IP protocol ● PROFINET IO Controller ● PROFINET IO Device ● SIMATIC communication ● Open IE communication ● Web server ● Media redundancy |
Yes; IPv4 Yes Yes Yes Yes; Optionally also encrypted Yes No |
| PROFINET IO Controller | |
| Services | |
| — Isochronous mode — Direct data exchange — IRT — PROFIenergy — Prioritized startup — Number of connectable IO Devices, max. — Number of connectable IO Devices for RT, max. — PROFINET Security Class |
No No No Yes; per user program No 32; in total, up to 1024 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET 32 32 8; in total across all interfaces 8 |
| Update time for IRT | |
| — for send cycle of 250 µs
— for send cycle of 500 µs |
250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 375 µs of the isochronous OB is decisive 500 µs to 8 ms 1 ms to 16 ms 2 ms to 32 ms 4 ms to 64 ms Update time = set “odd” send clock (any multiple of 125 µs: 375 µs, 625 µs … 3 875 µs) |
| Update time for RT | |
| — for send cycle of 250 µs — for send cycle of 500 µs — for send cycle of 1 ms — for send cycle of 2 ms — for send cycle of 4 ms |
250 µs to 128 ms 500 µs to 256 ms 1 ms to 512 ms 2 ms to 512 ms 4 ms to 512 ms |
| PROFINET IO Device | |
| Services | |
| — Isochronous mode — IRT — PROFIenergy — Shared device — Number of IO Controllers with shared device, max. — activation/deactivation of I-devices — Asset management record — PROFINET Security Class |
No Yes Yes; per user program Yes 4 Yes; per user program Yes; per user program SNMP Configuration and DCP Read Only |
| Interface types | |
| ● RJ 45 (Ethernet) ● Number of ports ● integrated switch |
Yes; X2 1 No |
| Protocols | |
| ● IP protocol ● PROFINET IO Controller ● PROFINET IO Device ● SIMATIC communication ● Open IE communication ● Web server ● Media redundancy |
Yes; IPv4 Yes Yes Yes Yes; Optionally also encrypted Yes No |
| PROFINET IO Controller | |
| Services | |
| — Isochronous mode — Direct data exchange — IRT — PROFIenergy — Prioritized startup — Number of connectable IO Devices, max. — Number of connectable IO Devices for RT, max. — PROFINET Security Class |
No No No Yes; per user program No 32; in total, up to 1024 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET 32 32 8; in total across all interfaces 8 |
| Update time for RT | |
| — for send cycle of 1 ms | 1 ms to 512 ms |
| PROFINET IO Device | |
| Services | |
| — Isochronous mode — IRT — PROFIenergy — Prioritized startup — Shared device — Number of IO Controllers with shared device, max. — activation/deactivation of I-devices — Asset management record — PROFINET Security Class |
No No Yes; per user program No Yes 4 Yes; per user program Yes; per user program SNMP Configuration and DCP Read Only |
| 3. Interface | |
| Interface types | |
| ● RS 485 ● Number of ports |
Yes; X3 1 |
| Protocols | |
| ● PROFIBUS DP master ● PROFIBUS DP device ● SIMATIC communication |
Yes No Yes |
| PROFIBUS DP master | |
| ● Number of connections, max. ● max. number of DP devices |
48; for the integrated PROFIBUS DP interface 125; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET |
| Services | |
| — Equidistance — Isochronous mode — activation/deactivation of DP devices |
Yes Yes Yes |
| Interface types | |
| RJ 45 (Ethernet) | |
| ● 100 Mbps ● Autonegotiation ● Autocrossing ● Industrial Ethernet status LED |
Yes Yes Yes Yes |
| RS 485 | |
| ● Transmission rate, max. | 12 Mbit/s |
| Protocols | |
| PROFIsafe | No |
| Number of connections | |
| ● Number of connections, max. ● Number of connections reserved for ES/HMI/web ● Number of connections via integrated interfaces ● Number of S7 routing paths |
256; via integrated interfaces of the CPU and connected CPs / CMs 10 128 16 |
| Redundancy mode | |
| ● H-Sync forwarding | Yes |
| Media redundancy | |
| — Media redundancy — MRP — MRP interconnection, supported |
only via 1st interface (X1) Yes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client Yes; as MRP ring node according to IEC 62439-2 Edition 3.0 Yes; Requirement: IRT 200 ms; For MRP, bumpless for MRPD 50 |
| SIMATIC communication | |
| ● PG/OP communication ● S7 routing ● Data record routing ● S7 communication, as server ● S7 communication, as client ● User data per job, max. |
Yes; encryption with TLS V1.3 pre-selected Yes Yes Yes Yes See online help (S7 communication, user data size) |
| Open IE communication | |
| ● TCP/IP — Data length, max. — several passive connections per port, supported ● ISO-on-TCP (RFC1006) — Data length, max. ● UDP — Data length, max. — UDP multicast ● DHCP ● DNS ● SNMP ● DCP ● LLDP ● Encryption |
Yes 64 kbyte Yes Yes 64 kbyte Yes 2 kbyte; 1 472 bytes for UDP broadcast Yes; max. 118 multicast circuits Yes Yes Yes Yes Yes Yes; Optional |
| Web server | |
| ● HTTP ● HTTPS ● web API — Number of sessions, max. — number of simultaneous HTTP calls, max. 4 — HTTP request body, max. |
Yes; Standard and user pages Yes; Standard and user pages 100 |
| OPC UA | |
| ● Runtime license required ● OPC UA Client — Application authentication — Security policies — User authentication |
Yes; “Medium” license required Yes; Data Access (registered Read/Write), Method Call Yes Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 “anonymous” or by user name & password 10 2000 300 20 100 1 |
| instructions for session management, per connection, max. — Number of simultaneous calls of the client instructions for data access, per connection, max. — Number of registerable nodes, max. — Number of registerable method calls of OPC_UA_MethodCall, max. — Number of inputs/outputs when calling OPC_UA_MethodCall, max. |
5 5000 20 |
| ● OPC UA Server | Yes; data access (read, write, subscribe), method call, alarms & condition (A&C), custom address space, role-based access control |
| — Application authentication — Security policies — User authentication — Number of inputs/outputs per server method, max. — Number of nodes for user-defined server interfaces, |
Yes available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss “anonymous” or by user name & password Yes 48 100 000 20 000 50 100 ms 100 ms 50; max. 20 concurrently running jobs each for asynchronous instructions OPC_UA_ServerMethodPre and OPC_UA_ServerMethodPost 20 4 000; for 1 s sampling interval and 1 s send interval 10 of each “Server interfaces” / “Companion specification” type and 20 of the type “Reference namespace” 30 000 Yes |
| Further protocols | |
| ● MODBUS | Yes; MODBUS TCP |
| Isochronous mode | |
| Equidistance | Yes |
| S7 message functions | |
| Number of login stations for message functions, max. | 64 |
| number of subscriptions, max. | 500 |
| number of tags/attributes for subscriptions, max. | 8 000 |
| Program alarms | Yes |
| Number of configurable program messages, max. | 10 000; Program messages are generated by the “Program_Alarm” block, ProDiag or GRAPH |
| Number of loadable program messages in RUN, max. | 10 000 |
| Number of simultaneously active program alarms ● Number of program alarms ● Number of alarms for system diagnostics ● Number of alarms for motion technology objects |
1 000 200 160 |
| Test commissioning functions | |
| Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 8 engineering systems |
| Status block | Yes; Up to 8 simultaneously (in total across all ES clients) |
| Single step | No |
| Number of breakpoints | 8 |
| Profiling | Yes |
| Status/control | |
| ● Status/control variable ● Variables ● Number of variables, max. — of which status variables, max. — of which control variables, max |
Yes Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters 200; per job |
| Forcing | |
| ● Forcing ● Forcing, variables ● Number of variables, max. |
Yes Peripheral inputs/outputs 200 |
| Diagnostic buffer | |
| ● present ● Number of entries, max. — of which powerfail-proof |
Yes 3200 500 |
| Traces | |
| ● Number of configurable Traces ● Memory size per trace, max. |
4 512 kbyte |
| Interrupts/diagnostics/status information | |
| Diagnostics indication LED | |
| ● RUN/STOP LED ● ERROR LED ● MAINT LED ● STOP ACTIVE LED ● Connection display LINK TX/RX |
Yes Yes Yes Yes Yes |
| Supported technology objects | |
| Motion Control
● Number of available Motion Control resources for |
Yes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool 2 400 40 11 20 |
| Controller ● PID_Compact ● PID_3Step ● PID-Temp |
Yes; Universal PID controller with integrated optimization Yes; PID controller with integrated optimization for valves Yes; PID controller with integrated optimization for temperature |
| Counting and measuring ● High-speed counter |
Yes |
| Standards, approvals, certificates | |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| Ecological footprint | |
| ● environmental product declaration | Yes |
| Global warming potential | |
| — global warming potential, (total) [CO2 eq] — global warming potential, (during production) [CO2 eq] — global warming potential, (during operation) [CO2 eq] — global warming potential, (after end of life cycle) [CO2 eq] |
102kg 26.5kg 76.7kg -0.898kg |
| product functions / security / header | |
| PROFINET Security Class | 1 |
| signed firmware update | Yes |
| Secure Boot | Yes |
| safely removing data | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
| ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. |
-30 °C; No condensation 60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off -30 °C; No condensation 40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off |
| Ambient temperature during storage/transportation | |
| ● min. ● max. |
-40 °C 70 °C |
| Altitude during operation relating to sea level | |
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| configuration / header | |
| configuration / programming / header | |
| Programming language | |
| — LAD — FBD — STL — SCL — CFC — GRAPH |
Yes Yes Yes Yes Yes Yes |
| Know-how protection | |
| ● User program protection/password protection ● Copy protection ● Block protection |
Yes Yes Yes |
| Access protection | |
| ● protection of confidential configuration data ● Password for display ● Protection level: Write protection ● Protection level: Read/write protection ● Protection level: Write protection for Failsafe ● Protection level: Complete protection ● User administration ● Number of users ● Number of groups ● Number of roles |
Yes Yes Yes Yes No Yes Yes; device-wide and centralized 100 100 50 |
| programming / cycle time monitoring / header | |
| ● lower limit ● upper limit |
adjustable minimum cycle time adjustable maximum cycle time |
| Dimensions | |
| Width | 70 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 469 g |